Product family

Final Distribution & Busbar

Distribution boards, metering equipment, cable branch boxes and busbar trunking systems.

Explore the evidence

Reports for identified models in this family

See the reported model and rating before opening a document. A family association is a navigation aid, not evidence that a report covers every product shown here.

English guide cover for report Z-14201-DC2501019
Test report

PV grid-connection box

Original reported model
GFBWX
Report / year
Z-14201-DC2501019 · 2025
Recorded reference
Rated voltage: 400 / 380 V; Ui: 690 V; Current range: 10-125 A; sample 125 A; Declared Icw: 6 kA (declared rating; short-circuit strength test marked N); Frequency: 50 Hz; Protection: Sample IP65 / operating face IP20C; lower IP labels described as same cabinet design; Circuits: 2
Standards stated in the report
GB/T 7251.3-2017
Explore this product family (not a model-equivalence claim) →
What this report covers
  • This is an independently prepared English reading guide, not an English report issued by the test laboratory. The complete Chinese original follows unchanged and governs interpretation.
  • Results apply to the submitted sample, stated configuration, test conditions and listed tests only. They are not a blanket certificate for all Minglang products or all project requirements.
  • Marketing product names identify a website range; the source report model, ratings and configuration must be matched before the evidence is used for an order.
  • No direct equivalence to website BXD2 / ML-MME400 is established. This is its own GFBWX PV grid-connection design.
  • The report summary marks both short-circuit strength and EMC N (not applicable or not performed). A declared Icw of 6 kA must not be described as a measured 6 kA short-circuit test in this report.
  • Use is limited to pollution degree 2. The source dynamic-load section prints inconsistent g and m/s2 values; request laboratory clarification before quoting acceleration.

4 guide pages + 60 source pages · 13.2 MB

English guide cover for report Z-14201-DC2600935
Test report

Outdoor CT-connected meter enclosure

Original reported model
PJF-HBT
Report / year
Z-14201-DC2600935 · 2026
Recorded reference
Rated voltage: 400 / 380 V; Ui: 690 V; Current range: 10-400 A; sample 400 A; Declared Icw: 10 kA (declared rating; short-circuit strength test marked N); Frequency: 50 Hz; Protection: IP44; IP34D label uses same design; Circuits: 1
Standards stated in the report
GB/T 7251.2-2023
Explore this product family (not a model-equivalence claim) →
What this report covers
  • This is an independently prepared English reading guide, not an English report issued by the test laboratory. The complete Chinese original follows unchanged and governs interpretation.
  • Results apply to the submitted sample, stated configuration, test conditions and listed tests only. They are not a blanket certificate for all Minglang products or all project requirements.
  • Marketing product names identify a website range; the source report model, ratings and configuration must be matched before the evidence is used for an order.
  • This is the 400 A configuration under GB/T 7251.2-2023, not the older 250 A PJF-HBT report under GB/T 7251.3-2017.
  • Short-circuit strength and EMC are marked N. Declared Icw 10 kA is not a measured short-circuit duty in this report.
  • The received-date field on p2 prints 2025.02.05, inconsistent with the 202602002 sample identity and 2026 completion date; this date should be clarified and is not used as a website claim.

4 guide pages + 64 source pages · 15.5 MB

English guide cover for report 02402-25I119C10188-S
Test report

Single-phase single-position meter enclosure

Original reported model
PXD1
Report / year
02402-25I119C10188-S · 2025
Recorded reference
Rated voltage: 230 / 220 V; Ui: 690 V; Current range: 10-60 A; sample 60 A; Declared Icw: 2 kA (declared rating; short-circuit strength test marked N); Frequency: 50 Hz; Protection: IP44 / operating face IP20C; IP34D label uses same design; Circuits: 1; Environment: Outdoor; pollution degree 2
Standards stated in the report
GB/T 7251.3-2017
Explore this product family (not a model-equivalence claim) →
What this report covers
  • This is an independently prepared English reading guide, not an English report issued by the test laboratory. The complete Chinese original follows unchanged and governs interpretation.
  • Results apply to the submitted sample, stated configuration, test conditions and listed tests only. They are not a blanket certificate for all Minglang products or all project requirements.
  • Marketing product names identify a website range; the source report model, ratings and configuration must be matched before the evidence is used for an order.
  • This is PXD1, not BXD2. It is family-level metering evidence only until a separate approved cross-reference establishes any new marketing model.
  • Summary p11 marks lifting, short-circuit strength and EMC N. Icw is a declared rating and not a tested short-circuit duty in this report.
  • The separate PXD1 utility-specification report 25I133C40078 has a different standard scope and must not be represented as an identical duplicate.

4 guide pages + 44 source pages · 4.8 MB