Product family

Power Quality & Control

Reactive-power compensation, automatic transfer and project-specific control panels.

Available platforms

Explore available products

Select a platform to review its applications, technical reference data, dimensions, resources and related products.

Explore the evidence

Reports for identified models in this family

See the reported model and rating before opening a document. A family association is a navigation aid, not evidence that a report covers every product shown here.

English guide cover for report SLVA-2022-05-100
Reissued type-test reports: 2022 tests, 2025 descriptive reissue

SLVA 330 + 50 kvar hybrid compensation - reissued type-test reports

Original reported model
SLVA-2500/07-330/50
Report / year
SLVA-2022-05-100 · 2025
Recorded reference
400 V, Ui 690 V, 50 Hz; horizontal busbar 2500 A / Icw 65 kA; compensation busbar 384 A + 72.2 A (SVG) / Icw 15 kA; 330 kvar capacitor compensation + 50 kvar SVG; single/three-phase plus SVG hybrid; filtering function stated. Indoor; enclosure IP4X, ventilation openings IP3XD, cabinet roof IP3X.
Standards stated in the report
GB/T 15576-2020 · GB/T 7251.1-2023 · GB/T 7251.2-2023 · GB/T 7251.8-2020 · client requirements · State Grid Corporation: Standardized Low-voltage Switchboard Design Scheme (2020 edition)
Explore this product family (not a model-equivalence claim) →
What this report covers
  • This SLVA compensation design is not GGJ and is not the SLVA distribution-cabinet design. There is no exact existing website product page; retain family-level matching only.
  • The first reissue records original 2022 tests and the 2025 name/address change; the 2025 date is not a new complete type test.
  • The horizontal-busbar 65 kA figure must not be transferred to the 15 kA compensation busbar.
  • The separate CQC change reports refer to different numbered originals; do not replace those missing originals with this Fangyuan report.
  • The website model is a commercial family name; the original laboratory model and tested arrangement remain controlling.
  • This is a Chinese GB/T report, not an IEC certificate or a blanket qualification of every offered configuration.
  • Pass, inherited pass, document-review pass and N (not applicable or not tested) are kept distinct.
  • Report scope has been reviewed against selected identity, change and result pages. A physical-page count alone is not a page-by-page completeness or authenticity audit.

8 guide pages + 216 source pages · 44.3 MB

English guide cover for report SLVA-2022-05-101
Reissued type-test reports: 2022 tests, 2025 descriptive reissue

SLVA 360 kvar compensation - reissued type-test reports

Original reported model
SLVA-2500/08-360
Report / year
SLVA-2022-05-101 · 2025
Recorded reference
400 V, Ui 690 V, 50 Hz; horizontal busbar 2500 A / Icw 65 kA; compensation busbar 418.2 A / Icw 15 kA; 360 kvar single/three-phase compensation; no harmonic-suppression or filtering function. Indoor; enclosure IP4X, ventilation openings IP3XD, cabinet roof IP3X.
Standards stated in the report
GB/T 15576-2020 · GB/T 7251.1-2023 · GB/T 7251.2-2023 · GB/T 7251.8-2020 · client requirements · State Grid Corporation: Standardized Low-voltage Switchboard Design Scheme (2020 edition)
Explore this product family (not a model-equivalence claim) →
What this report covers
  • This SLVA compensation design is not GGJ and is not the SLVA distribution-cabinet design. There is no exact existing website product page; retain family-level matching only.
  • The first reissue records original 2022 tests and the 2025 name/address change; the 2025 date is not a new complete type test.
  • The horizontal-busbar 65 kA figure must not be transferred to the 15 kA compensation busbar.
  • The separate CQC change reports refer to different numbered originals; do not replace those missing originals with this Fangyuan report.
  • The website model is a commercial family name; the original laboratory model and tested arrangement remain controlling.
  • This is a Chinese GB/T report, not an IEC certificate or a blanket qualification of every offered configuration.
  • Pass, inherited pass, document-review pass and N (not applicable or not tested) are kept distinct.
  • Report scope has been reviewed against selected identity, change and result pages. A physical-page count alone is not a page-by-page completeness or authenticity audit.

8 guide pages + 212 source pages · 41.5 MB